How Many ADA Parking Spaces Does a Commercial Lot Need?
A lot with 1 to 25 total spaces needs 1 accessible space. From there it is 2 spaces up to 50, 3 up to 75, and 4 up to 100, and at least one of every six accessible spaces has to be van accessible. That answers it for most commercial lots. What surprises people is the sizing: Oregon requires a 9 foot space with a 6 foot aisle, which is bigger than the federal minimum, so a lot striped to the national numbers can still fail here.
| Total spaces in the lot | Minimum accessible spaces |
|---|---|
| 1 to 25 | 1 |
| 26 to 50 | 2 |
| 51 to 75 | 3 |
| 76 to 100 | 4 |
| 101 to 150 | 5 |
| 151 to 200 | 6 |
| 201 to 300 | 7 |
| 301 to 400 | 8 |
| 401 to 500 | 9 |
| 501 to 1,000 | 2 percent of the total |
| 1,001 and over | 20, plus 1 for each 100 or fraction over 1,000 |
From the 2010 ADA Standards for Accessible Design, section 208.2. Oregon and Washington both adopt the same counts in their state building codes. Fractions always round up.
We build commercial projects and tenant improvements across Portland and Southwest Washington, and parking is one of the quieter ways a project gets held up. The count is easy. The dimensions, the slope, and the signs are where lots actually fail, and restriping a finished lot costs real money.
What is ADA parking?
"ADA parking" is the set of reserved spaces a commercial property has to provide under the Americans with Disabilities Act, along with the rules for how big they are, how they connect to the building, and how they are marked. It is not a courtesy space. The ADA parking requirements are enforceable, they apply to new construction and to alterations, and in Oregon and Washington the state building code layers its own version on top.
Two things make a space count. It has to meet the size and slope rules below, and it has to connect to an accessible route into the building without forcing anyone to travel behind parked cars. A correctly sized stall at the far end of a lot with a curb in the way is not compliant.
The van rule: one in six
At least one of every six accessible spaces, or fraction of six, must be van accessible. The fraction part matters. A lot with 3 accessible spaces still needs 1 van space, because 3 is a fraction of 6. A lot with 7 accessible spaces needs 2.
You may see an older figure of one in eight. That was the 1991 guideline and it is out of date. Current work in both Oregon and Washington runs on one in six.
Space and aisle sizes, and why the state matters
This is the part that catches people, because the federal standard is a floor and Oregon builds on top of it. Here is the same requirement in all three places:
| Dimension | Federal ADA | Oregon | Washington |
|---|---|---|---|
| Accessible space width | 96 inches (8 ft) | 9 ft minimum | 96 inches (8 ft) |
| Access aisle, car space | 60 inches (5 ft) | 6 ft minimum | 60 inches (5 ft) |
| Van space | 132 in wide with a 60 in aisle, or 96 in wide with a 96 in aisle | 9 ft space with an 8 ft aisle | 96 in space with a 96 in aisle |
| Vertical clearance on van routes | 98 inches | 98 inches | 98 inches |
| Maximum slope, any direction | 1:48 (about 2.08 percent) | 1:48 | 1:48 |
| Sign height to bottom of sign | 60 inches | 7 ft on a post, 5 ft on a building | 60 inches |
Federal figures from the 2010 ADA Standards (502.2, 502.3, 502.4, 502.5, 502.6). Oregon figures from the Oregon Transportation Commission Standards for Accessible Parking Places (2023), which the Oregon Structural Specialty Code adopts in place of the national dimensions. Washington figures from the Washington State Building Code amendments 1101.2.7 and 1101.2.8.
Read that table row by row before you stripe anything. A lot laid out to the federal 8 foot space and 5 foot aisle is legal in Washington and undersized in Oregon. It is the same drawing, two different answers, and the fix after paving is a full restripe.
The Oregon rules people don't see coming
Oregon does not simply adopt the national parking dimensions. Under ORS 447.233 the Oregon Transportation Commission sets its own standards, and the state building code points at them. Four things differ from what a national spec will tell you:
- Bigger spaces and aisles. 9 feet wide with a 6 foot access aisle, and 8 feet of aisle where the space is van accessible or reserved for wheelchair users.
- A third sign that does not exist federally. Oregon uses a WHEELCHAIR USER ONLY sign (OR7-8c) alongside the standard reserved parking sign and the van accessible rider. It marks spaces with an 8 foot aisle that only vehicles with a wheelchair user placard may use.
- Signs go higher on posts. 7 feet, plus or minus 3 inches, from the ground to the bottom of the sign. On a building or pier it is 5 feet minimum. The federal standard says 60 inches, so a post set to the national number is low here.
- Every access aisle gets a NO PARKING legend painted in it, white or yellow and retroreflective, and the aisle sits on the passenger side unless two spaces share one between them.
None of these are hard to build. They are only expensive when nobody checks until the lot is poured and striped.
What Washington does differently
Washington keeps the 96 inch space, so an Oregon layout is always wide enough to work across the river, but not the other way around. The one real Washington amendment is on van spaces: the state requires a 96 inch access aisle for them rather than allowing the federal alternative of a 132 inch space with a narrower 60 inch aisle. In practice that means every van stall in Washington is the wide aisle version.
The two that fail inspection most often
Slope. Accessible spaces and their aisles cannot exceed 1:48, roughly 2.08 percent, in any direction. That is flatter than a lot needs to be to drain well, so a surface built purely for drainage will often miss it. Slope is measured after paving, which is the worst possible time to find out.
The route, not just the stall. The 98 inch vertical clearance applies to the van space, its access aisle, and the vehicle route serving them, so a canopy, a low soffit, or a parking structure beam anywhere along the drive can put a compliant stall out of compliance. Check the whole path a van takes to get there.
Where parking fits in a build-out
Parking counts get reviewed with everything else when your permit package goes through plan review, alongside occupant load and fixture counts. If you are working through those numbers too, our guide to how many bathrooms a commercial building needs covers the same kind of math indoors, and who pulls the permit explains how review actually runs in Portland, Multnomah County, Washington County, and Vancouver.
If you are taking a leased space, worth knowing: bringing a non compliant lot up to standard is usually a landlord and tenant negotiation, and it is the kind of item a tenant improvement allowance may or may not cover. Settle it before signing, not after.
Looking at a lot right now? We have been building commercial projects across the Portland metro since 2008. Send us the space count and the address, or call (360) 326-2747, and we will tell you how many accessible spaces it needs and whether the striping you have will pass.
Frequently asked questions
How many ADA parking spaces are required?
It scales with the size of the lot. A lot with 1 to 25 total spaces needs 1 accessible space, 26 to 50 needs 2, 51 to 75 needs 3, 76 to 100 needs 4, and it keeps climbing from there. Lots of 501 to 1,000 spaces need 2 percent of the total, and above 1,000 the rule is 20 spaces plus one more for each additional 100.
How many of them have to be van accessible?
At least one of every six accessible spaces, or fraction of six, must be van accessible. So a lot with 1 to 6 accessible spaces needs 1 van space, and a lot with 7 to 12 accessible spaces needs 2. Oregon and Washington both use the same one in six ratio.
What size does an ADA parking space have to be?
The federal minimum is 96 inches wide with a 60 inch access aisle. Oregon is larger and requires at least 9 feet wide with a 6 foot aisle, and 8 feet of aisle for a van space. Washington keeps the 96 inch space but requires a 96 inch aisle for van spaces.
Is Oregon different from the federal ADA rules?
Yes, and it catches people out. Oregon sets its own parking dimensions through the Oregon Transportation Commission, and they are bigger than the federal minimums: 9 feet for the space instead of 8, and 6 feet of access aisle instead of 5. Oregon also uses a WHEELCHAIR USER ONLY sign that does not exist in the federal standard, and post mounted signs go at 7 feet, not 5.
How high does the accessible parking sign go?
Under the federal standard the bottom of the sign sits at least 60 inches above the ground. In Oregon a post mounted sign goes higher, at 7 feet plus or minus 3 inches to the bottom of the sign, and 5 feet minimum when the sign is mounted on a building or pier.
How flat does the parking space have to be?
Very flat. Accessible spaces and their access aisles cannot slope more than 1:48, which is about 2.08 percent, in any direction. This is the requirement that most often fails on a resurfaced lot, because a slope that drains well can still be too steep to pass.
The bottom line
The count is the easy half and the table above settles it. The half that costs money is the sizing, and it depends on which side of the river you are building on: Oregon wants 9 by 6, Washington accepts 8 by 5, and both want one van space in every six. Check the lot against those numbers before it is paved, because slope and stall width are not things you fix with a paint gun.
Modern Northwest builds commercial construction and build-outs across Portland and SW Washington, and site accessibility is part of the permit package we handle on every job. Reach out for a free walkthrough.
Modern Northwest · Commercial general contractor since 2008 · (360) 326-2747
Serving Portland, Beaverton, Hillsboro, Gresham, Tigard, Lake Oswego and Vancouver, WA. Licensed in Oregon and Washington.
Sources
- ADA.gov, "Accessible Parking Spaces" (2010 ADA Standards summary)
- U.S. Access Board, "Chapter 5: Parking Spaces" (ADA Standards guide)
- ADA National Network, "Accessible Parking" factsheet
- Oregon Transportation Commission, "Standards for Accessible Parking Places" (ODOT, 2023)
- Oregon Structural Specialty Code, Chapter 11 Accessibility (1106.5), via UpCodes
- Washington State Building Code, Chapter 11 Accessibility (1101.2.7, 1101.2.8, 1106.6), via UpCodes